Voltage Drop Calculator

Voltage Drop Calculator

Popular AI Skill PRO

Enter Calculation

Formula

Vdrop=2·ρ·Length (m)·Current (A)Area (mm2)V_{drop} = \frac{2 \cdot \rho \cdot \text{Length (m)} \cdot \text{Current (A)}}{{{\text{Area (mm}^2\text{)}}}}
Usage stats

Advertisement

Results

Voltage Drop
7.73
volts
Voltage Drop (%) 6.44 %
Voltage at Load End 112.27 V
Compared with the 3% guideline Above 3%
Wire resistance at 75 °C 1.9315 ohms per 1,000 ft

Report an error on this page

What Is Voltage Drop?

Voltage drop is the reduction in voltage along a cable caused by the conductor's electrical resistance. As current flows through a wire, some energy is lost as heat, so the voltage available at the load end is lower than at the source. Excessive voltage drop can cause dim lighting, motor overheating, and equipment malfunction. On the U.S. page the calculator works in AWG wire sizes and feet (switch to mm² and metres for metric cables). A widely used design target in the U.S. is no more than 3% drop on a branch circuit and 5% in total from the service to the farthest outlet.

Diagram of a wire run from source to load showing higher voltage at source and lower voltage at load
Voltage drops along a conductor as current flows from source to load.

How to Use It

Choose US (AWG, feet) or metric sizes, the conductor material (copper or aluminum) and whether the circuit is single- or three-phase. Enter the load current in amps and the source voltage, then the wire size and one-way length (AWG and feet, or mm² and metres). The tool returns the absolute voltage drop, the drop as a percentage, and the resulting voltage at the load end.

The Formula Explained

We use the resistivity form: $$V_{drop} = \dfrac{k \cdot \rho \cdot L \cdot I}{A}$$ Here \(\rho\) (rho) is the resistivity — about \(0.0172\ \Omega\cdot\text{mm}^2/\text{m}\) for copper and \(0.0282\ \Omega\cdot\text{mm}^2/\text{m}\) for aluminum at 20°C. The factor \(k\) accounts for circuit topology: 2 for a single-phase circuit (current travels out and back, doubling the conductor length) and \(\sqrt{3}\) (\(\approx 1.732\)) for a balanced three-phase line-to-line calculation.

Advertisement
Labeled diagram of the voltage drop formula variables on a conductor cross-section and length
The formula variables: current I, length L, conductor area A, and material resistivity.

Voltage drop with AWG wire (US)

For AWG wire the calculator works out the wire's resistance instead of using a fixed table: the diameter of AWG size n is \(d = 0.005 \times 92^{(36-n)/39}\) inches, its area in circular mils is \(d^2\) (d in mils), and the resistance per 1,000 ft is the resistivity divided by that area. It uses annealed copper at 10.371 Ω·cmil/ft at 20 °C with a temperature coefficient of 0.00393 per °C (NIST Handbook 100), and aluminum at 61% of that conductivity, both raised to a 75 °C conductor temperature. The drop is then

$$V_{drop} = \frac{k \times L \times I \times R}{1000}$$

where L is the one-way length in feet, I the current in amps, R the resistance in ohms per 1,000 ft, and k is 2 for single-phase or \(\sqrt{3}\) for three-phase.

Example: a 20 A load on 100 ft of 12 AWG copper at 120 V. The wire has about 1.93 Ω per 1,000 ft at 75 °C, so \(V_{drop} = 2 \times 100 \times 20 \times 1.93 \div 1000 \approx 7.73\) V, or 6.4% — more than the 3% target. 10 AWG brings it to about 4.9 V (4.0%), and 8 AWG to about 3.1 V (2.5%).

Size (AWG) Copper, Ω per 1,000 ft at 75 °C Aluminum, Ω per 1,000 ft at 75 °C
14 3.071 5.058
12 1.932 3.181
10 1.215 2.000
8 0.764 1.258
6 0.480 0.791
4 0.302 0.498
2 0.190 0.313
1/0 0.120 0.197
4/0 0.060 0.098

These are calculated values for solid conductors; stranded wire of the same size has a slightly higher resistance (about 2%), so treat results as estimates. The 3% and 5% figures come from informational notes in NFPA 70, the National Electrical Code (210.19(A)); they are recommendations for efficient operation, not mandatory limits.

Worked Example

A copper cable carries 20 A over a 30 m one-way run with a 4 mm² conductor on a 230 V single-phase supply. $$V_{drop} = \frac{2 \times 0.0172 \times 30 \times 20}{4} = 5.16\ \text{V}$$ That is \(\dfrac{5.16}{230} \times 100 = 2.24\%\), leaving 224.84 V at the load — within the typical 5% limit.

Advertisement

Related tools

FAQ

Why multiply length by 2? Current must flow to the load and back, so a single-phase circuit's effective conductor length is twice the one-way run.

Copper vs aluminum? Aluminum has higher resistivity, so it drops more voltage for the same size; you typically need a larger cross-section.

Does temperature matter? Yes — resistivity rises with temperature. In metric mode the tool uses 20 °C values, so hot conductors drop slightly more; in AWG mode it uses a 75 °C conductor temperature, the usual basis for U.S. circuit design.

Sources & References

  • Copper Wire Tables (NBS Handbook 100) — National Institute of Standards and Technology (NIST), formerly National Bureau of Standards. Annealed copper standard 10.371 ohm-circular mil/ft at 20 C, temperature coefficient 0.00393 per C at 20 C; AWG diameters in the ratio 92^(1/39) per gage. The calculator derives resistance at 75 C from these (aluminum at 61% IACS). · Verified 2026-11-16
  • NFPA 70, National Electrical Code (2023 edition) — National Fire Protection Association (NFPA). Standard reference: informational note recommending branch-circuit conductors sized for no more than 3% voltage drop at the farthest outlet and no more than 5% for feeders and branch circuits combined; a recommendation, not a requirement. Cited by section (free-access text requires sign-in). · Verified 2026-11-16
Last updated:

Most popular in Physics and Engineering

View all Physics and Engineering calculators