What Is Voltage Drop?
Voltage drop is the reduction in voltage along a cable caused by the conductor's electrical resistance. As current flows through a wire, some energy is lost as heat, so the voltage available at the load end is lower than at the source. Excessive voltage drop can cause dim lighting, motor overheating, and equipment malfunction. On the U.S. page the calculator works in AWG wire sizes and feet (switch to mm² and metres for metric cables). A widely used design target in the U.S. is no more than 3% drop on a branch circuit and 5% in total from the service to the farthest outlet.
How to Use It
Choose US (AWG, feet) or metric sizes, the conductor material (copper or aluminum) and whether the circuit is single- or three-phase. Enter the load current in amps and the source voltage, then the wire size and one-way length (AWG and feet, or mm² and metres). The tool returns the absolute voltage drop, the drop as a percentage, and the resulting voltage at the load end.
The Formula Explained
We use the resistivity form: $$V_{drop} = \dfrac{k \cdot \rho \cdot L \cdot I}{A}$$ Here \(\rho\) (rho) is the resistivity — about \(0.0172\ \Omega\cdot\text{mm}^2/\text{m}\) for copper and \(0.0282\ \Omega\cdot\text{mm}^2/\text{m}\) for aluminum at 20°C. The factor \(k\) accounts for circuit topology: 2 for a single-phase circuit (current travels out and back, doubling the conductor length) and \(\sqrt{3}\) (\(\approx 1.732\)) for a balanced three-phase line-to-line calculation.
Voltage drop with AWG wire (US)
For AWG wire the calculator works out the wire's resistance instead of using a fixed table: the diameter of AWG size n is \(d = 0.005 \times 92^{(36-n)/39}\) inches, its area in circular mils is \(d^2\) (d in mils), and the resistance per 1,000 ft is the resistivity divided by that area. It uses annealed copper at 10.371 Ω·cmil/ft at 20 °C with a temperature coefficient of 0.00393 per °C (NIST Handbook 100), and aluminum at 61% of that conductivity, both raised to a 75 °C conductor temperature. The drop is then
$$V_{drop} = \frac{k \times L \times I \times R}{1000}$$where L is the one-way length in feet, I the current in amps, R the resistance in ohms per 1,000 ft, and k is 2 for single-phase or \(\sqrt{3}\) for three-phase.
Example: a 20 A load on 100 ft of 12 AWG copper at 120 V. The wire has about 1.93 Ω per 1,000 ft at 75 °C, so \(V_{drop} = 2 \times 100 \times 20 \times 1.93 \div 1000 \approx 7.73\) V, or 6.4% — more than the 3% target. 10 AWG brings it to about 4.9 V (4.0%), and 8 AWG to about 3.1 V (2.5%).
| Size (AWG) | Copper, Ω per 1,000 ft at 75 °C | Aluminum, Ω per 1,000 ft at 75 °C |
|---|---|---|
| 14 | 3.071 | 5.058 |
| 12 | 1.932 | 3.181 |
| 10 | 1.215 | 2.000 |
| 8 | 0.764 | 1.258 |
| 6 | 0.480 | 0.791 |
| 4 | 0.302 | 0.498 |
| 2 | 0.190 | 0.313 |
| 1/0 | 0.120 | 0.197 |
| 4/0 | 0.060 | 0.098 |
These are calculated values for solid conductors; stranded wire of the same size has a slightly higher resistance (about 2%), so treat results as estimates. The 3% and 5% figures come from informational notes in NFPA 70, the National Electrical Code (210.19(A)); they are recommendations for efficient operation, not mandatory limits.
Worked Example
A copper cable carries 20 A over a 30 m one-way run with a 4 mm² conductor on a 230 V single-phase supply. $$V_{drop} = \frac{2 \times 0.0172 \times 30 \times 20}{4} = 5.16\ \text{V}$$ That is \(\dfrac{5.16}{230} \times 100 = 2.24\%\), leaving 224.84 V at the load — within the typical 5% limit.
Related tools
- Watts to amps: the current your load draws, the starting point for voltage drop.
- Wire size and ampacity: the wire gauge a load current needs.
- Breaker size: the breaker rating for the circuit.
- Max lights per circuit: how many fixtures one circuit can carry.
FAQ
Why multiply length by 2? Current must flow to the load and back, so a single-phase circuit's effective conductor length is twice the one-way run.
Copper vs aluminum? Aluminum has higher resistivity, so it drops more voltage for the same size; you typically need a larger cross-section.
Does temperature matter? Yes — resistivity rises with temperature. In metric mode the tool uses 20 °C values, so hot conductors drop slightly more; in AWG mode it uses a 75 °C conductor temperature, the usual basis for U.S. circuit design.