Superheat and Subcooling Calculator

Superheat and Subcooling Calculator

Growing AI Skill PRO

Enter Calculation

Formula

SH=Tsuc−TeSC=Tc−Tliqwhere{Tsuc=Suction Line Temp (°F)Tliq=Liquid Line Temp (°F)Te=Tsat(Suction Pressure (psig))Tc=Tsat(Liquid Pressure (psig))Tsat(P)=T1+10·ln⁡(P+14.696)−ln⁡(P1+14.696)ln⁡(P2+14.696)−ln⁡(P1+14.696)P1,P2=table points for RefrigerantΔSH=SH−Target SH (°F)ΔSC=SC−Target SC (°F)\begin{gathered} \text{SH} = T_{suc} - T_{e} \qquad \text{SC} = T_{c} - T_{liq} \\[1.5em] \text{where}\quad \left\{ \begin{aligned} T_{suc} &= \text{Suction Line Temp (°F)} \\ T_{liq} &= \text{Liquid Line Temp (°F)} \\ T_{e} &= T_{sat}\left(\text{Suction Pressure (psig)}\right) \\ T_{c} &= T_{sat}\left(\text{Liquid Pressure (psig)}\right) \\ T_{sat}(P) &= T_1 + 10\cdot\frac{\ln(P+14.696)-\ln(P_1+14.696)}{\ln(P_2+14.696)-\ln(P_1+14.696)} \\ P_1,P_2 &= \text{table points for } \text{Refrigerant} \\ \Delta\text{SH} &= \text{SH} - \text{Target SH (°F)} \\ \Delta\text{SC} &= \text{SC} - \text{Target SC (°F)} \end{aligned} \right. \end{gathered}
Usage stats

Advertisement

Results

Superheat
12
°F above evaporator saturation
Subcooling
10
°F below condenser saturation
Superheat is within 2°F of target.
Subcooling is within 2°F of target.
Evaporator saturation temp 40 °F
Condenser saturation temp 100 °F
Superheat vs target 2 °F
Subcooling vs target 0 °F

Report an error on this page

What superheat and subcooling tell you

Superheat and subcooling are the two key numbers technicians use to judge refrigerant charge and system health. Superheat is how far the refrigerant vapor leaving the evaporator is above its boiling (saturation) temperature. Subcooling is how far the liquid leaving the condenser is below its condensing temperature. This calculator converts your gauge pressures into saturation temperatures for R-410A, R-22, R-134a or R-404A and then works out both values.

Refrigeration cycle showing where suction and liquid line temperature and pressure are measured
Measure suction pressure and temperature at the evaporator outlet, and liquid pressure and temperature at the condenser outlet.

How to use it

Select the refrigerant, then enter the suction pressure (psig) and the suction line temperature measured near the service valve or evaporator outlet. Next enter the liquid line pressure and the liquid line temperature measured near the condenser outlet. Optionally set your target superheat and subcooling from the manufacturer data plate, and the tool shows how far you are from each target.

The formulas

The saturation temperature \(T_{sat}\) is found from the pressure using a pressure-temperature table, interpolated on the logarithm of absolute pressure (psig plus 14.696).

$$\text{SH} = T_{\text{suction line}} - T_{\text{sat}}(P_{\text{suction}})$$$$\text{SC} = T_{\text{sat}}(P_{\text{liquid}}) - T_{\text{liquid line}}$$

Table values are approximate bubble/dew point data. For zeotropic blends such as R-404A, always confirm against the manufacturer chart.

Advertisement
Pressure-enthalpy diagram showing superheat beyond the vapor curve and subcooling beyond the liquid curve
Superheat is the temperature above saturated vapor; subcooling is the temperature below saturated liquid.

Worked example

An R-410A system reads 118.8 psig on the suction side, which corresponds to \(T_{sat} = 40\,{}^{\circ}\text{F}\). The suction line measures 52 °F.

$$\text{SH} = 52 - 40 = 12\,{}^{\circ}\text{F}$$

The liquid pressure is 317.6 psig, equal to a saturation temperature of 100 °F, and the liquid line is 90 °F.

$$\text{SC} = 100 - 90 = 10\,{}^{\circ}\text{F}$$

A superheat of 12 °F and subcooling of 10 °F are both typical for a healthy system.

Advertisement

Interpreting Your Superheat and Subcooling Readings

Superheat (SH) is the suction-line temperature minus the evaporator saturation temperature. Subcooling (SC) is the condenser saturation temperature minus the liquid-line temperature. Neither number means much alone: always read SH, SC, suction pressure, head pressure and airflow together, and compare them with the equipment manufacturer's charging chart or nameplate target. Targets vary by model, so the calculator's Target SH and Target SC fields should come from that documentation.

Which number to charge by

  • Fixed-orifice / piston systems: charge to the manufacturer's target superheat (usually read from a chart based on indoor wet-bulb and outdoor dry-bulb temperature). Subcooling is a secondary check.
  • TXV / EEV systems: the valve holds superheat roughly constant, so charge to the manufacturer's target subcooling. Superheat is a secondary check that the valve is controlling properly.

Reading combinations and likely causes

Reading Likely causes Other clues
High SH, low SC Undercharge (the most common cause of this pair) Low suction and head pressure; bubbles in sight glass if fitted
High SH, normal or high SC Restricted metering device, restricted filter drier or liquid line; TXV underfeeding or hunting Low suction pressure; temperature drop across the drier or kink
Low SH, high SC Overcharge; on a fixed orifice, also an oversized orifice High head pressure; risk of liquid floodback to the compressor
Low SH, normal SC Low evaporator airflow (dirty filter or coil, slow blower) or a TXV overfeeding Low suction pressure; coil icing
Low SH, low SC Weak compressor (valves not pumping fully) or heavy load High suction pressure with low head pressure
High SC (apparent), high head pressure Non-condensables (air) in the system, or overcharge Head pressure is higher than the condenser air temperature explains; the pressure-derived saturation temperature is inflated, so calculated SC looks high
Low SC, high head pressure Dirty condenser or poor condenser airflow, with other faults High condensing temperature relative to outdoor air

Does low subcooling always mean undercharge?

No. Low subcooling is a symptom, not a diagnosis. Undercharge is a common cause, but low subcooling also occurs with a weak compressor (head pressure too low), a metering device that is too large or stuck open, a TXV that is flooding, or a very high-load condition. Measurement errors matter too: a poorly insulated or badly placed temperature clamp, an uncalibrated gauge, the wrong refrigerant selected, or reading before the system has stabilized (typically 10–15 minutes of operation) can all produce misleading values. If subcooling is low but superheat is also low, adding refrigerant is the wrong move. Check airflow, compressor performance and the metering device first.

This is general information, not professional advice. Refrigerant handling is regulated in many countries and generally requires certified technicians; always follow the equipment manufacturer's instructions and local regulations.

FAQ

What is a normal superheat?

Fixed-orifice systems are charged by superheat, often 10 to 20 °F depending on indoor wet-bulb and outdoor temperature. Always follow the equipment charging chart.

What is a normal subcooling?

Systems with a thermostatic expansion valve are typically charged to 8 to 12 °F of subcooling unless the manufacturer states otherwise.

Does low subcooling always mean undercharge?

Usually, but a dirty condenser, bad compressor valves or metering device faults can also change readings, so check airflow and other symptoms before adding refrigerant.

Last updated:

Most popular in Physics and Engineering

View all Physics and Engineering calculators