What is the Evaporation Rate Calculator?
This tool estimates how fast water evaporates from an open surface — such as a swimming pool, pond, tank, or wet floor — using the classic mass-transfer relationship $$g_h = \Theta \cdot A \cdot \left( x_s - x \right)$$ The result tells you how many kilograms of water leave the surface each hour, which is essential for sizing pool dehumidifiers, ventilation systems, and HVAC loads.
How to use it
Enter four values: the evaporation coefficient \(\Theta\) (kg/m²·h), the wetted surface area \(A\) (m²), the saturated humidity ratio \(x_s\) of air directly at the water surface, and the humidity ratio \(x\) of the surrounding room air (both in kg water per kg dry air). The calculator multiplies them to give the hourly evaporation rate and also reports the daily total.
The formula explained
The evaporation coefficient \(\Theta\) captures air velocity over the surface; for a still indoor pool it is often around 25 kg/m²·h, rising with air movement. The driving force \((x_s - x)\) is the difference in humidity ratio — evaporation only occurs while the air can still absorb moisture. When the room air is saturated (\(x = x_s\)) the difference is zero and evaporation stops.
Worked example
For a 1 m² wet surface with \(\Theta = 25\), \(x_s = 0.025\) kg/kg and \(x = 0.010\) kg/kg: the difference is 0.015 kg/kg, so $$g_h = 25 \times 1 \times 0.015 = 0.375 \text{ kg/h}$$ or about 9 kg per day.
Saturated Humidity Ratio xₛ by Water Temperature
The table gives the saturated humidity ratio xₛ (kg water per kg dry air) at sea-level pressure (101.325 kPa). Values are computed from the saturation vapour pressure pₛ with \(x_s = 0.622 \cdot \frac{p_s}{101.325 - p_s}\), where pₛ is in kPa. They are rounded to 3 significant figures.
| Water temperature (°C) | pₛ (kPa, approx.) | xₛ (kg/kg) |
|---|---|---|
| 15 | 1.706 | 0.0107 |
| 20 | 2.339 | 0.0147 |
| 24 | 2.985 | 0.0189 |
| 25 | 3.170 | 0.0201 |
| 26 | 3.363 | 0.0214 |
| 28 | 3.782 | 0.0241 |
| 30 | 4.247 | 0.0272 |
| 35 | 5.627 | 0.0366 |
Getting x from room air: look up xₛ at the air temperature, then multiply by relative humidity φ (as a fraction): \(x \approx \varphi \cdot x_s(T_{air})\). Example: air at 26 °C and 60 % RH gives \(x \approx 0.60 \cdot 0.0214 \approx 0.0128\) kg/kg. This approximation is good at moderate humidity. For precise work use a psychrometric chart. Values at other pressures or altitudes differ.
Typical Evaporation Coefficient (Θ) Values
Θ is in kg/(m²·h), used with humidity ratios in kg/kg. The values below are engineering rules of thumb, of the kind used in pool-ventilation guidance such as VDI 2089 (a German guideline). They vary between sources and standards, so check the guideline that applies to your application and country.
| Surface condition | Typical Θ (kg/m²·h), approximate |
|---|---|
| Still or covered water (no use) | about 5 or less |
| Private or residential pool, light use | about 15 |
| Public pool, normal activity | about 20–28 |
| Pool with heavy activity or water features | about 28–35 or more |
| Surface with strong air movement | Often estimated as \(\Theta \approx 25 + 19\,v\) (v = air speed in m/s over the surface), e.g. about 44 at 1 m/s and about 63 at 2 m/s |
Use the lower end for calm, rarely used water and the higher end for turbulent, heavily used or splashing surfaces.
Comparing Evaporation Across Scenarios
All cases use A = 1 m² and \(g_h = \Theta \cdot A \cdot (x_s - x)\). Daily values are \(g_h \times 24\). Humidity ratios are in kg/kg.
| Scenario | Θ | xₛ | x | Calculation | gₕ (kg/h) | kg/day |
|---|---|---|---|---|---|---|
| Private pool, light use (28 °C water) | 15 | 0.0241 | 0.0120 | 15 · 1 · (0.0241 − 0.0120) = 15 · 0.0121 | 0.1815 | 4.36 |
| Public pool, normal use (28 °C water) | 28 | 0.0241 | 0.0140 | 28 · 1 · (0.0241 − 0.0140) = 28 · 0.0101 | 0.2828 | 6.79 |
| Heavy activity (30 °C water) | 35 | 0.0272 | 0.0150 | 35 · 1 · (0.0272 − 0.0150) = 35 · 0.0122 | 0.427 | 10.25 |
| Near-saturated room (28 °C water) | 28 | 0.0241 | 0.0240 | 28 · 1 · (0.0241 − 0.0240) = 28 · 0.0001 | 0.0028 | 0.067 |
| Condensation: x > xₛ (20 °C water) | 15 | 0.0147 | 0.0180 | 15 · 1 · (0.0147 − 0.0180) = 15 · (−0.0033) | −0.0495 | −1.19 |
A negative result means the air holds more moisture than the water surface can sustain, so water condenses onto the surface instead of evaporating. A result near zero means the air is almost saturated at the water temperature. For other areas, multiply by A. For example, a 50 m² surface in the public-pool case loses about 14.1 kg/h.
Constants and Reference Values Used
| Quantity | Value | Notes |
|---|---|---|
| Ratio of molar masses, water / air | 0.622 | Used when calculating humidity ratio x |
| Standard atmospheric pressure | 101.325 kPa | Reference pressure for humidity ratio |
| Latent heat of vaporization of water | ≈ 2,454 kJ/kg at 20 °C | Decreases as temperature rises |
| Latent heat of vaporization of water | ≈ 2,430 kJ/kg at 30 °C | Used for the ≈ 0.68 kW per kg/h estimate |
| Density of water | ≈ 998 kg/m³ at 20 °C | So 1 kg ≈ 1 L |
| Time conversion | 1 kg/h = 24 kg/day | Also ≈ 24 L/day |
| Energy conversion | 1 kW = 3,600 kJ/h | Converts kJ/h to kW |
Unit conventions
- Θ (evaporation coefficient): kg/m²·h
- A (water surface area): m²
- xs, x (humidity ratios): kg water per kg dry air
- gh (evaporation rate): kg/h
FAQ
What value should I use for \(\Theta\)? Use roughly 25 kg/m²·h for still air, and higher (40–60+) for surfaces with significant airflow or activity such as occupied pools.
How do I find the humidity ratios? Read them from a psychrometric chart: \(x_s\) from the water-surface temperature (assumed saturated) and \(x\) from the room's temperature and relative humidity.
Can evaporation be negative? If \(x\) exceeds \(x_s\) the formula gives a negative value, meaning condensation onto the surface rather than evaporation.