Horsepower to Amps Calculator

Horsepower to Amps Calculator

Leading AI Skill PRO

Enter Calculation

Formula

I=746×HPV×Eff %100×PFI = \frac{746 \times \text{HP}}{\text{V} \times \dfrac{\text{Eff \%}}{100} \times \text{PF}}

Example

I=746×5230×90100×0.9≈20.02I = \frac{746 \times 5}{230 \times \dfrac{90}{100} \times 0.9} \approx 20.02
Usage stats

Advertisement

Results

Current Draw
20.02
amps (A)
Real power 3,730 W

Report an error on this page

What is the Horsepower to Amps Calculator?

This tool converts mechanical horsepower (HP) into the electrical current, measured in amps (A), that a motor draws from its supply. Because one mechanical horsepower equals 746 watts, knowing the HP, supply voltage, motor efficiency, and power factor lets you size breakers, wiring, and overload protection correctly. It supports DC, AC single-phase, and AC three-phase systems.

How to use it

Enter the motor's rated horsepower and the supply voltage. Choose the current type (DC, single-phase, or three-phase). Then enter the motor efficiency as a percentage (typical motors run 80–95%) and the power factor (typically 0.8–0.95 for AC; power factor is ignored for DC). The calculator returns the full-load current in amps and the equivalent real power in watts.

Three flat panels comparing DC, single-phase, and three-phase current formulas
Current calculation differs for DC, single-phase, and three-phase supplies.

The formula explained

The base relationship is current = power ÷ voltage. Real electrical power needed equals HP × 746 ÷ efficiency, because some input energy is lost as heat. For AC, the power factor (PF) accounts for the phase difference between voltage and current, so we divide by PF. Three-phase systems add a \(\sqrt{3}\) (≈1.732) factor because of the line-to-line voltage relationship:

Single-phase: $$I = \frac{746 \times \text{HP}}{\text{V} \times \dfrac{\text{Eff \%}}{100} \times \text{PF}}$$Three-phase: $$I = \frac{746 \times \text{HP}}{\sqrt{3} \times \text{V} \times \dfrac{\text{Eff \%}}{100} \times \text{PF}}$$DC: $$I = \frac{746 \times \text{HP}}{\text{V} \times \dfrac{\text{Eff \%}}{100}}$$

Advertisement

Worked example

A 5 HP single-phase motor on 230 V with 90% efficiency and 0.9 power factor: \(5 \times 746 = 3730\ \text{W}\). Then $$3730 \div (230 \times 0.90 \times 0.90) = 3730 \div 186.3 \approx 20.02\ \text{A}.$$

Flat diagram showing horsepower input converted to current using voltage, efficiency, and power factor
How motor power, voltage, efficiency, and power factor combine to determine current draw.

Typical Full-Load Current by Horsepower and Voltage

The table lists full-load current (amps) for common motor sizes. The values come from the US National Electrical Code (NEC, NFPA 70): Table 430.248 for single-phase motors and Table 430.250 for three-phase induction motors. A dash means the NEC does not list that size at that voltage.

HP 1-phase 115 V 1-phase 230 V 3-phase 208 V 3-phase 230 V 3-phase 460 V
0.5 9.8 4.9 2.4 2.2 1.1
1 16 8 4.6 4.2 2.1
2 24 12 7.5 6.8 3.4
3 34 17 10.6 9.6 4.8
5 56 28 16.7 15.2 7.6
7.5 80 40 24.2 22 11
10 100 50 30.8 28 14
15 – 68 46.2 42 21
20 – 88 59.4 54 27

Why these may differ from the calculator: the NEC tables use their own assumed efficiency and power factor, and the values are deliberately conservative. They are intended for sizing conductors and protection. The calculator uses the efficiency and power factor you enter, so it will often give a lower current. The nameplate full-load amps (FLA) of the actual motor takes precedence over both the table and the calculator.

Typical Efficiency and Power Factor Ranges

These are general ranges for typical motors. Always check the nameplate or datasheet of your motor.

Motor type / size Typical full-load efficiency
Small fractional HP (below 1 HP) about 60–80%
1–10 HP about 82–91%
Larger motors (above about 10 HP) above 92%
NEMA Premium / IE3 class higher than standard-efficiency motors of the same size
  • Power factor: induction motors typically run at about 0.7–0.85 at full load. It falls at partial load, sometimes well below 0.7 when the motor is lightly loaded.
  • DC motors: power factor does not apply, so use PF = 1 (the calculator’s DC mode ignores it). Only efficiency matters.
  • Standards: efficiency levels for North American motors are defined in NEMA MG-1 (for example, NEMA Premium). The international efficiency classes IE1–IE4 are defined in IEC 60034-30.
Advertisement

Interpreting Your Result

The calculated current is a theoretical full-load running current. It is the current the motor draws when delivering its rated horsepower at the efficiency and power factor you entered. It is not the starting (inrush) current, which for across-the-line starting of an induction motor is commonly several times higher (often cited as roughly 5–8 times) but lasts only a short time.

Comparing with other values:

  • Nameplate FLA: the manufacturer’s figure for that specific motor. If your calculated value is close to it, your efficiency and PF inputs are reasonable.
  • NEC tabulated values (US): usually higher than a calculation with real-world efficiency and PF, because the tables are conservative.

Example (three-phase): 5 HP at 460 V, 90% efficiency, PF 0.85:

$$I = \frac{746 \times 5}{\sqrt{3} \times 460 \times 0.90 \times 0.85} = \frac{3730}{609.5} \approx 6.1\ \text{A}$$

The NEC value for a 5 HP, 460 V three-phase motor is 7.6 A, which is higher for the reasons above.

Single-phase vs. three-phase: for the same HP, voltage, efficiency and PF, a single-phase motor draws about \(\sqrt{3} \approx 1.73\) times the current of a three-phase motor, because the three-phase formula divides by an extra factor of \(\sqrt{3}\). Doubling the voltage roughly halves the current.

Use in NEC rules (US): under NEC Article 430, conductors for a continuous-duty motor are generally sized at 125% of the full-load current (Art. 430.22). Motor overload protection and branch-circuit short-circuit and ground-fault protection are sized under separate rules in Article 430, using their own multipliers and tables. These rules are specific to the US NEC; other countries use different codes. This is general information, not a design or safety instruction. Have installations specified by a qualified electrician or engineer.

FAQ

Why is efficiency included? A motor draws more electrical power than it delivers mechanically. Dividing by efficiency converts output HP into the larger input power the supply must provide.

What if I don't know the power factor? Use 0.8–0.85 for typical induction motors, or 1 for purely resistive/DC loads. The PF field is ignored for DC.

Is this the running current or starting current? This gives full-load running current. Motor inrush at startup can be 5–8× higher, so size protection accordingly.

Last updated:

Most popular in Physics and Engineering

View all Physics and Engineering calculators