kVA Calculator

kVA Calculator

Growing AI Skill PRO

Enter Calculation

Formula

kVA=Voltage (V)×Current (A)1000\text{kVA} = \frac{\text{Voltage (V)} \times \text{Current (A)}}{1000}

Example

kVA=230×101000=2.3\text{kVA} = \frac{230 \times 10}{1000} = 2.3
Usage stats

Advertisement

Results

Apparent Power
2.3
kVA
Apparent power (VA) 2,300 VA

Report an error on this page

What is a kVA Calculator?

This kVA calculator finds the apparent power of an electrical circuit from its voltage and current. Apparent power, measured in volt-amperes (VA) or kilovolt-amperes (kVA), is the product of the RMS voltage and RMS current in an AC system. Unlike real power (kW), apparent power includes both the working power and the reactive power required by inductive and capacitive loads, which is why transformers, generators and UPS units are rated in kVA.

How to use it

Select whether your system is single-phase or three-phase, enter the voltage in volts and the current in amperes, then read the apparent power in kVA. For single-phase the calculator multiplies voltage by current; for three-phase it includes the \(\sqrt{3}\) (\(\approx 1.732\)) factor that accounts for the phase relationship between the three line conductors.

Power triangle showing apparent power kVA, real power kW and reactive power kVAR
The power triangle relates apparent power (kVA), real power (kW) and reactive power (kVAR).

The formula explained

Single-phase:

$$\text{kVA} = \dfrac{V \times I}{1000}$$

Three-phase:

$$\text{kVA} = \dfrac{\sqrt{3} \times V \times I}{1000}$$

where \(V\) is the line-to-line voltage and \(I\) is the line current. Dividing by 1000 converts volt-amperes to kilovolt-amperes. To convert kVA to real power (kW), multiply by the power factor.

Advertisement

Worked example

A three-phase motor runs on 400 V drawing 50 A. Apparent power:

$$\text{kVA} = \dfrac{1.732 \times 400 \times 50}{1000} = \dfrac{34{,}640}{1000} \approx 34.64\ \text{kVA}$$

A single-phase load at 230 V drawing 10 A is

$$\text{kVA} = \dfrac{230 \times 10}{1000} = 2.3\ \text{kVA}$$
Diagram comparing single-phase and three-phase kVA formulas with voltage and current
Apparent power (kVA) formulas for single-phase and three-phase circuits.

Standard Voltages and Typical kVA Ratings

Nominal supply voltages and standard equipment ratings differ by country and by standard (IEC in much of the world, IEEE/ANSI in North America). The tables below show commonly encountered values, not a universal rule. Always check local regulations and the equipment nameplate.

Common nominal system voltages

Type Nominal voltage Where commonly used
Single-phase 120 V North America (general outlets)
Single-phase 230 V Europe and many other regions (IEC 60038 nominal)
Single-phase 240 V North America (split-phase, line-to-line); also used as a nominal figure in several countries
Three-phase 208 V North America (120/208 V systems, line-to-line)
Three-phase 380 V Some countries and older installations
Three-phase 400 V Europe and many other regions (400/230 V)
Three-phase 415 V Several countries, e.g. Australia and India (415/240 V)
Three-phase 480 V North America (277/480 V industrial and commercial)

Three-phase voltages are line-to-line values.

Typical standard kVA ratings

Equipment Examples of standard or common ratings (kVA)
Three-phase distribution transformers (IEC-style preferred series) 50, 100, 160, 250, 400, 630, 1000, 1600
Three-phase pad/dry-type transformers (IEEE/ANSI-style, North America) 15, 30, 45, 75, 112.5, 150, 225, 300, 500, 750, 1000
Single-phase distribution transformers (North America) 10, 15, 25, 37.5, 50, 75, 100, 167
Generator sets (varies by manufacturer) e.g. 25, 50, 75, 100, 150, 250, 500, 1000

Exact available sizes depend on the manufacturer, region and standard, so use these only as a general guide.

kVA for Common Loads and Voltages

Single-phase: \(\text{kVA} = \frac{V \times I}{1000}\). Three-phase (line-to-line voltage, balanced load): \(\text{kVA} = \frac{\sqrt{3} \times V \times I}{1000}\), where \(\sqrt{3} \approx 1.732\). The kW columns use \(\text{kW} = \text{kVA} \times \text{PF}\).

Phase Voltage Current Calculation kVA kW at PF 0.8 kW at PF 0.9
Single 120 V 20 A 120 × 20 / 1000 2.40 1.92 2.16
Single 230 V 10 A 230 × 10 / 1000 2.30 1.84 2.07
Single 230 V 32 A 230 × 32 / 1000 7.36 5.89 6.62
Single 240 V 50 A 240 × 50 / 1000 12.00 9.60 10.80
Three 208 V 100 A 1.732 × 208 × 100 / 1000 36.03 28.82 32.42
Three 400 V 50 A 1.732 × 400 × 50 / 1000 34.64 27.71 31.18
Three 415 V 100 A 1.732 × 415 × 100 / 1000 71.88 57.50 64.69
Three 480 V 200 A 1.732 × 480 × 200 / 1000 166.28 133.02 149.65

Worked check for the 400 V, 50 A three-phase row: \(\frac{1.732 \times 400 \times 50}{1000} = \frac{34641}{1000} \approx 34.64\) kVA. Values are rounded to two decimals.

Advertisement

Interpreting Your kVA Result

kVA is apparent power: the product of voltage and current, regardless of how much of that current does useful work. Transformers, generators and UPS systems are rated in kVA because their heating and winding limits depend on current and voltage, not on the load's power factor (PF).

  • Real power: \(\text{kW} = \text{kVA} \times \text{PF}\).
  • Reactive power: \(\text{kVAR} = \sqrt{\text{kVA}^2 - \text{kW}^2}\).
  • Power factor: \(\text{PF} = \frac{\text{kW}}{\text{kVA}}\), a value between 0 and 1.

Example: a 100 kVA supply at PF 0.8 delivers \(100 \times 0.8 = 80\) kW, and the reactive power is \(\sqrt{100^2 - 80^2} = \sqrt{3600} = 60\) kVAR.

A lower power factor means more kVA is needed for the same kW. For an 80 kW load, PF 0.8 requires \(80 / 0.8 = 100\) kVA, while PF 0.95 requires about \(80 / 0.95 \approx 84.2\) kVA. This is why improving power factor can free up capacity.

Equipment ratings usually include some margin above the calculated load, to allow for motor starting currents, future growth, temperature and altitude derating, and non-linear loads. The size of the margin depends on the application and the applicable standards.

This is general information, not engineering-design advice. Have a qualified engineer or electrician size equipment for a real installation and check local codes.

FAQ

What's the difference between kVA and kW? kVA is apparent power; kW is real (usable) power. \(\text{kW} = \text{kVA} \times \text{power factor}\).

Why use \(\sqrt{3}\) for three-phase? The \(\sqrt{3}\) factor relates line-to-line voltage and line current in a balanced three-phase system to total apparent power.

Is voltage line-to-line or line-to-neutral? For the three-phase formula above, use the line-to-line voltage (e.g. 400 V or 415 V).

Last updated:

Most popular in Physics and Engineering

View all Physics and Engineering calculators