What Is the Solar Power Calculator?
This calculator estimates the size of a solar photovoltaic (PV) system you need and how much energy it will generate. It is a universal tool — it works anywhere, as long as you know your local peak sun hours. Enter your daily electricity consumption, the average peak sun hours for your location, and a performance ratio that accounts for real-world losses (inverter, wiring, temperature, dust, shading).
How to Use It
Provide three numbers: \(U\) = daily energy usage in kWh, \(H\) = peak sun hours per day, and \(PR\) = performance ratio (typically \(0.75\)–\(0.85\)). The calculator returns the recommended array size in kW and the expected daily, monthly, and yearly energy production.
The Formula
The required system size is the daily demand divided by the productive sun hours and the performance ratio:
$$P_{kW} = \frac{U}{H \times PR}$$where \(P_{kW}\) = system size in kilowatts, \(U\) = daily usage (kWh), \(H\) = peak sun hours, and \(PR\) = performance ratio. Daily generation from that array is:
$$E_{day} = P_{kW} \times H \times PR$$
Worked Example
Suppose you use \(30\) kWh per day, your region averages \(5\) peak sun hours, and \(PR = 0.8\). The required system size is:
$$P_{kW} = \frac{30}{5 \times 0.8} = \frac{30}{4} = 7.5\,\text{kW}$$That system produces \(E_{day} = 7.5 \times 5 \times 0.8 = 30\) kWh per day, about \(913\) kWh per month and \(10{,}950\) kWh per year.
Typical Peak Sun Hours by Region
Peak sun hours (PSH) are the equivalent hours per day at 1 kW/m² of irradiance, which is numerically the same as daily insolation in kWh/m²/day. The values below are approximate annual averages for broad regions. Real sites differ with latitude, cloud cover, altitude, panel tilt and orientation, and seasonal variation is large. Winter values can be far below the annual average, and summer values far above it.
| Region / climate | Approx. annual-average peak sun hours (kWh/m²/day) |
|---|---|
| Northern Europe | about 2.5 – 3.5 |
| Central Europe | about 3 – 4 |
| Northern United States | about 4 – 4.5 |
| Southwestern United States | about 6 – 7 |
| Middle East / North Africa | about 5.5 – 7 |
| Tropical regions | about 4.5 – 6 |
For a site-specific figure, use a local resource such as NREL PVWatts (strongest for the US and many other locations) or the Global Solar Atlas (worldwide). Both let you enter tilt and orientation and show monthly values.
System Size Comparison Across Scenarios
The table fixes daily usage at \(U = 30\) kWh/day and varies peak sun hours \(H\) and performance ratio \(PR\). Required size is $$\text{kW} = \frac{U}{H \times PR}$$ and yearly output is \(\text{kW} \times H \times PR \times 365\). Because each system is sized exactly to the load, the yearly output always equals \(30 \times 365 = 10{,}950\) kWh. A real system should be sized larger than this minimum or rounded up to whole panels.
| Peak sun hours (H) | PR | H × PR | Required size (kW) | Yearly output (kWh) |
|---|---|---|---|---|
| 3 | 0.70 | 2.10 | 14.29 | 10,950 |
| 3 | 0.80 | 2.40 | 12.50 | 10,950 |
| 3 | 0.85 | 2.55 | 11.76 | 10,950 |
| 4 | 0.70 | 2.80 | 10.71 | 10,950 |
| 4 | 0.80 | 3.20 | 9.38 | 10,950 |
| 4 | 0.85 | 3.40 | 8.82 | 10,950 |
| 5 | 0.70 | 3.50 | 8.57 | 10,950 |
| 5 | 0.80 | 4.00 | 7.5 | 10,950 |
| 5 | 0.85 | 4.25 | 7.06 | 10,950 |
| 6 | 0.70 | 4.20 | 7.14 | 10,950 |
| 6 | 0.80 | 4.80 | 6.25 | 10,950 |
| 6 | 0.85 | 5.10 | 5.88 | 10,950 |
Example check for the highlighted row: \(30 \div (5 \times 0.80) = 30 \div 4.00 = 7.5\) kW. Going from 3 to 6 sun hours roughly halves the required array size.
Practical Sizing Tips
- Round up to whole panels. Divide the array size by the panel wattage. For example, 7.5 kW ÷ 400 W = 18.75, so use about 19 panels (≈ 7.6 kW).
- Add a margin of roughly 10–20%. Panels degrade by about 0.5% per year (about 10% over 20 years), and loads often grow, for example with an EV or heat pump. A 7.5 kW base need becomes roughly 8.25–9 kW with this margin.
- Check roof area. Allow roughly 1.6–2 m² per panel. 19 panels need about 30–38 m² of usable, unshaded space, excluding setbacks, vents and obstructions.
- Consider the worst month. If you need to cover winter demand, use winter peak sun hours instead of the annual average. This gives a larger array, and the system will overproduce in summer.
- Check the inverter and local grid rules. The inverter is commonly sized close to the array's DC rating, and utilities or regulators may limit system size, export capacity and net-metering terms. Requirements vary by country and utility.
- Use realistic inputs. Take peak sun hours for your tilt and orientation from a tool such as PVWatts or the Global Solar Atlas. Performance ratios of about 0.75–0.85 are common, depending on shading, temperature, wiring and inverter losses.
This is general information, not professional advice. Have a qualified installer assess your site and local regulations before buying.
FAQ
What are peak sun hours? The number of hours per day when sunlight intensity averages \(1000\,\text{W/m}^2\). It is not the same as daylight hours and varies by location and season.
What performance ratio should I use? A well-designed rooftop system typically achieves \(0.75\)–\(0.85\). Use a lower value for hot climates or shaded roofs.
Does this size the battery? No — this estimates panel array size and generation. Battery sizing depends on your desired backup duration and depth of discharge.