Solar Power Calculator

Solar Power Calculator

Popular AI Skill PRO

Enter Calculation

Formula

System Size (kW)=Daily Usage (kWh)Peak Sun Hours×Performance Ratio\text{System Size (kW)} = \frac{\text{Daily Usage (kWh)}}{\text{Peak Sun Hours} \times \text{Performance Ratio}}

Example

System Size (kW)=305×0.8=7.5\text{System Size (kW)} = \frac{30}{5 \times 0.8} = 7.5
Usage stats

Advertisement

Results

Recommended System Size
7.5
kW
Daily Generation 30 kWh
Monthly Generation 913.13 kWh
Yearly Generation 10,957.5 kWh

Report an error on this page

What Is the Solar Power Calculator?

This calculator estimates the size of a solar photovoltaic (PV) system you need and how much energy it will generate. It is a universal tool — it works anywhere, as long as you know your local peak sun hours. Enter your daily electricity consumption, the average peak sun hours for your location, and a performance ratio that accounts for real-world losses (inverter, wiring, temperature, dust, shading).

How to Use It

Provide three numbers: \(U\) = daily energy usage in kWh, \(H\) = peak sun hours per day, and \(PR\) = performance ratio (typically \(0.75\)–\(0.85\)). The calculator returns the recommended array size in kW and the expected daily, monthly, and yearly energy production.

The Formula

The required system size is the daily demand divided by the productive sun hours and the performance ratio:

$$P_{kW} = \frac{U}{H \times PR}$$

where \(P_{kW}\) = system size in kilowatts, \(U\) = daily usage (kWh), \(H\) = peak sun hours, and \(PR\) = performance ratio. Daily generation from that array is:

$$E_{day} = P_{kW} \times H \times PR$$
Advertisement
Diagram showing sunlight hitting a solar panel and powering a house, with factors U, H, and PR
How usage (U), peak sun hours (H), and performance ratio (PR) determine the required system size.

Worked Example

Suppose you use \(30\) kWh per day, your region averages \(5\) peak sun hours, and \(PR = 0.8\). The required system size is:

$$P_{kW} = \frac{30}{5 \times 0.8} = \frac{30}{4} = 7.5\,\text{kW}$$

That system produces \(E_{day} = 7.5 \times 5 \times 0.8 = 30\) kWh per day, about \(913\) kWh per month and \(10{,}950\) kWh per year.

Typical Peak Sun Hours by Region

Peak sun hours (PSH) are the equivalent hours per day at 1 kW/m² of irradiance, which is numerically the same as daily insolation in kWh/m²/day. The values below are approximate annual averages for broad regions. Real sites differ with latitude, cloud cover, altitude, panel tilt and orientation, and seasonal variation is large. Winter values can be far below the annual average, and summer values far above it.

Region / climate Approx. annual-average peak sun hours (kWh/m²/day)
Northern Europe about 2.5 – 3.5
Central Europe about 3 – 4
Northern United States about 4 – 4.5
Southwestern United States about 6 – 7
Middle East / North Africa about 5.5 – 7
Tropical regions about 4.5 – 6

For a site-specific figure, use a local resource such as NREL PVWatts (strongest for the US and many other locations) or the Global Solar Atlas (worldwide). Both let you enter tilt and orientation and show monthly values.

System Size Comparison Across Scenarios

The table fixes daily usage at \(U = 30\) kWh/day and varies peak sun hours \(H\) and performance ratio \(PR\). Required size is $$\text{kW} = \frac{U}{H \times PR}$$ and yearly output is \(\text{kW} \times H \times PR \times 365\). Because each system is sized exactly to the load, the yearly output always equals \(30 \times 365 = 10{,}950\) kWh. A real system should be sized larger than this minimum or rounded up to whole panels.

Peak sun hours (H) PR H × PR Required size (kW) Yearly output (kWh)
3 0.70 2.10 14.29 10,950
3 0.80 2.40 12.50 10,950
3 0.85 2.55 11.76 10,950
4 0.70 2.80 10.71 10,950
4 0.80 3.20 9.38 10,950
4 0.85 3.40 8.82 10,950
5 0.70 3.50 8.57 10,950
5 0.80 4.00 7.5 10,950
5 0.85 4.25 7.06 10,950
6 0.70 4.20 7.14 10,950
6 0.80 4.80 6.25 10,950
6 0.85 5.10 5.88 10,950

Example check for the highlighted row: \(30 \div (5 \times 0.80) = 30 \div 4.00 = 7.5\) kW. Going from 3 to 6 sun hours roughly halves the required array size.

Advertisement

Practical Sizing Tips

  • Round up to whole panels. Divide the array size by the panel wattage. For example, 7.5 kW ÷ 400 W = 18.75, so use about 19 panels (≈ 7.6 kW).
  • Add a margin of roughly 10–20%. Panels degrade by about 0.5% per year (about 10% over 20 years), and loads often grow, for example with an EV or heat pump. A 7.5 kW base need becomes roughly 8.25–9 kW with this margin.
  • Check roof area. Allow roughly 1.6–2 m² per panel. 19 panels need about 30–38 m² of usable, unshaded space, excluding setbacks, vents and obstructions.
  • Consider the worst month. If you need to cover winter demand, use winter peak sun hours instead of the annual average. This gives a larger array, and the system will overproduce in summer.
  • Check the inverter and local grid rules. The inverter is commonly sized close to the array's DC rating, and utilities or regulators may limit system size, export capacity and net-metering terms. Requirements vary by country and utility.
  • Use realistic inputs. Take peak sun hours for your tilt and orientation from a tool such as PVWatts or the Global Solar Atlas. Performance ratios of about 0.75–0.85 are common, depending on shading, temperature, wiring and inverter losses.

This is general information, not professional advice. Have a qualified installer assess your site and local regulations before buying.

FAQ

What are peak sun hours? The number of hours per day when sunlight intensity averages \(1000\,\text{W/m}^2\). It is not the same as daylight hours and varies by location and season.

What performance ratio should I use? A well-designed rooftop system typically achieves \(0.75\)–\(0.85\). Use a lower value for hot climates or shaded roofs.

Does this size the battery? No — this estimates panel array size and generation. Battery sizing depends on your desired backup duration and depth of discharge.

Last updated:

Most popular in Physics and Engineering

View all Physics and Engineering calculators