Water Cooling Calculator

Water Cooling Calculator

Leading AI Skill PRO

Enter Calculation

Formula

Q=m˙·c·ΔTwhere{m˙=Flow rate (L/min)60000×Density (kg per m3)c=Specific heat (J/kg-C)ΔT=Temp rise (C)\begin{gathered} Q = \dot{m} \cdot c \cdot \Delta T \\[1.5em] \text{where}\quad \left\{ \begin{aligned} \dot{m} &= \dfrac{\text{Flow rate (L/min)}}{60000} \times \text{Density (kg per m3)} \\ c &= \text{Specific heat (J/kg-C)} \\ \Delta T &= \text{Temp rise (C)} \end{aligned} \right. \end{gathered}
Show calculation steps (1)
  1. Heat Removal Rate (kW)

    QkW=Flow rate (L/min)×Density (kg per m3)×Specific heat (J/kg-C)×Temp rise (C)60000×1000Q_{kW} = \frac{\text{Flow rate (L/min)} \times \text{Density (kg per m3)} \times \text{Specific heat (J/kg-C)} \times \text{Temp rise (C)}}{60000 \times 1000}

    Same heat balance expressed in kilowatts by dividing the watt result by 1000

Usage stats

Advertisement

Results

Heat Removed by Coolant
697.67
watts (W)
Heat removed 0.698 kW
Mass flow rate 0.0167 kg/s
Formula Q = ṁ × c × ΔT

Report an error on this page

What is the Water Cooling Calculator?

This calculator determines how much heat a liquid cooling loop can remove using the fundamental heat transfer equation \(Q = \dot{m} \cdot c \cdot \Delta T\). It is widely used for PC water cooling, industrial chillers, laser cooling, engine cooling jackets and any closed loop where a pumped fluid carries away thermal energy. The result is given in watts and kilowatts.

Diagram of a water cooling loop showing flow through a heat source and a radiator
A water cooling loop absorbs heat from a source and carries it away through circulating water.

How to use it

Enter the coolant flow rate in litres per minute, the temperature rise (\(\Delta T\)) between the coolant outlet and inlet in °C, the coolant density (water ≈ 1000 kg/m³) and its specific heat (water ≈ 4186 J/kg·°C). The tool converts the volumetric flow into a mass flow rate and multiplies by specific heat and temperature difference to give the heat removed.

The formula explained

The mass flow rate \(\dot{m}\) (kg/s) is the volumetric flow divided by 1000 (L→m³) and 60 (min→s), times density:

$$\dot{m} = \frac{\text{flow (L/min)}}{1000 \times 60} \cdot \rho$$

Multiplying \(\dot{m}\) by the specific heat \(c\) and the temperature change \(\Delta T\) gives \(Q\) in watts — the rate of heat energy carried away by the fluid. A larger flow rate or a larger temperature rise both remove more heat.

Advertisement
Diagram showing inlet and outlet temperatures across a heated block with mass flow
Heat removed equals mass flow rate times specific heat times the temperature rise (\(\Delta T = T_{out} - T_{in}\)).

Worked example

A loop runs water at 2 L/min with a 10 °C rise. Mass flow:

$$\dot{m} = \left(2 \div 1000 \div 60\right) \times 1000 = 0.03333 \text{ kg/s}$$

Heat removed:

$$Q = 0.03333 \times 4186 \times 10 \approx \mathbf{1395 \text{ W } (1.4 \text{ kW})}$$

Doubling the flow to 4 L/min doubles the heat removed to about 2790 W.

Density and Specific Heat of Common Coolants

Enter these values in the density and specheat fields when your loop is not pure water. The figures below are typical values at about 20–25 °C. Glycol mixtures are given by mass concentration and are approximate.

Coolant Density (kg/m³) Specific heat (J/kg·°C)
Pure water ≈ 998–1000 ≈ 4182–4186
25% propylene glycol / water ≈ 1015–1020 ≈ 3900–4000
50% propylene glycol / water ≈ 1030–1040 ≈ 3500
30% ethylene glycol / water ≈ 1035–1040 ≈ 3700
50% ethylene glycol / water ≈ 1065–1070 ≈ 3300
Mineral / transformer oil (for comparison) ≈ 850–890 ≈ 1800–2000

Values change with temperature and with glycol concentration, and inhibitor packages shift them slightly. Always check the manufacturer's datasheet for your exact fluid and operating temperature. Note that glycol mixtures carry less heat per litre than water, so the same flow and ΔT remove less power.

Heat Removal at Different Flow Rates and Temperature Rises

The table is for water with ρ = 1000 kg/m³ and c = 4186 J/kg·°C. Each value uses \(Q = \frac{\text{L/min}}{60} \times 4186 \times \Delta T\), which is about 69.77 W per (L/min·°C). Results are rounded to the nearest watt.

Flow rate (L/min) ΔT = 2 °C (W) ΔT = 5 °C (W) ΔT = 10 °C (W)
1 140 349 698
2 279 698 1395
4 558 1395 2791
8 1116 2791 5581

Worked check for 2 L/min and 10 °C: \(\dot{m} = \frac{2}{60} \times 1000 / 1000 = 0.03333\) kg/s, so \(Q = 0.03333 \times 4186 \times 10 \approx 1395\) W. Q scales linearly: doubling either the flow or the temperature rise doubles the heat removed. Reaching the same heat load with a smaller ΔT needs proportionally more flow.

Advertisement

Unit Conversions for Heat and Flow

Quantity Equivalent
1 W 3.412 BTU/hr
1 kW 3412 BTU/hr
1 ton of refrigeration 3.517 kW = 12,000 BTU/hr
1 US GPM 3.785 L/min
1 L/min 0.264 US GPM
1 m³/h 16.67 L/min
1 kcal/h 1.163 W

Example: a 1395 W result equals about \(1395 \times 3.412 \approx 4760\) BTU/hr, or roughly 0.40 tons of refrigeration. GPM here means US gallons per minute.

FAQ

What density and specific heat should I use? Pure water near room temperature: 1000 kg/m³ and 4186 J/kg·°C. A water/glycol mix has lower specific heat (~3300–3800 J/kg·°C) and slightly higher density.

Is \(\Delta T\) the inlet or outlet temperature? \(\Delta T\) is the difference (outlet minus inlet) — the temperature the coolant gained while passing through the heat source.

How do I convert to BTU/hr? Multiply the watt result by 3.412.

Last updated:

Most popular in Physics and Engineering

View all Physics and Engineering calculators