Compression Ratio
3.24
: 1
Discharge (absolute) 274.7 psia
Suction (absolute) 84.7 psia

What Is the HVAC Compression Ratio?

The compression ratio of an HVAC or refrigeration compressor is the ratio of the absolute discharge (high-side) pressure to the absolute suction (low-side) pressure. It tells you how hard the compressor is working to raise the refrigerant from the evaporating pressure to the condensing pressure. A higher ratio means more work, higher discharge temperatures, lower volumetric efficiency, and greater wear. Typical air-conditioning systems run a ratio around 2:1 to 4:1, while low-temperature refrigeration can climb well above 10:1.

Compressor with low-pressure suction inlet and high-pressure discharge outlet
Compression ratio compares absolute discharge pressure to absolute suction pressure across the compressor.

How to Use This Calculator

Enter the discharge (head) pressure and the suction pressure. Choose whether your readings are gauge (psig, what a service gauge shows) or already absolute (psia). If gauge, the tool adds atmospheric pressure to convert to absolute before dividing. You can adjust the atmospheric pressure for altitude; sea level is about \(14.7\) psi.

The Formula

The compression ratio uses absolute pressures, where \(P_{atm}\) = atmospheric pressure:

$$CR = \frac{P_{discharge,abs}}{P_{suction,abs}} = \frac{P_{discharge,gauge} + P_{atm}}{P_{suction,gauge} + P_{atm}}$$

Here \(P_{discharge,gauge}\) and \(P_{suction,gauge}\) are gauge readings in psig, and \(P_{atm}\) is atmospheric pressure in psi.

Advertisement
Diagram showing absolute pressure equals gauge pressure plus atmospheric pressure
Pressures must be converted to absolute (gauge plus atmospheric) before computing the ratio.

Worked Example

Suppose discharge pressure is \(260\) psig and suction pressure is \(70\) psig at sea level (\(P_{atm}=14.7\)):

$$CR = \frac{260 + 14.7}{70 + 14.7} = \frac{274.7}{84.7} = 3.24$$

So this compressor operates at a compression ratio of about \(3.24:1\), normal for an air-conditioning application.

FAQ

Why use absolute pressure instead of gauge? Compression ratio is a true pressure ratio, so both pressures must be referenced to a perfect vacuum (absolute). Using gauge values gives a wrong, inflated ratio.

What is a high compression ratio? Above roughly 10:1 you risk excessive discharge temperatures, oil breakdown, and reduced efficiency. Low-temp systems often need two-stage compression to manage this.

Does altitude matter? Yes. At higher elevations atmospheric pressure drops, which slightly changes the absolute conversion. Enter your local atmospheric pressure for best accuracy.