What Is Thermal Resistance?
Thermal resistance (R) measures how strongly a material layer opposes the conductive flow of heat. A higher R value means better insulation, since the material lets less heat pass for a given temperature difference. It is a fundamental quantity in building physics, electronics cooling, and heat-transfer engineering. This calculator uses the steady-state conduction relationship to find R from a layer's geometry and material properties.
How to Use This Calculator
Enter three values: the thickness of the material L in metres (the distance heat must travel), the thermal conductivity k in W/m·K (a material property), and the area A in square metres through which heat flows. The calculator returns the thermal resistance R in kelvin per watt (K/W) and the thermal conductance \(U = 1/R\) in W/K.
The Formula Explained
The governing equation is $$R = \frac{\text{Thickness } L}{\text{Conductivity } k \cdot \text{Area } A}$$ Resistance grows with thickness because heat has farther to travel, and it shrinks with higher conductivity or larger area because both make it easier for heat to pass. Materials with low \(k\) (like foam or fibreglass, \(k \approx 0.04\) W/m·K) produce high resistance and are good insulators, while metals (high \(k\)) produce very low resistance.
Worked Example
Consider a 0.1 m thick foam panel with conductivity \(k = 0.04\) W/m·K covering an area of 10 m². Then $$R = \frac{0.1}{0.04 \times 10} = \frac{0.1}{0.4} = 0.25 \text{ K/W}$$ The conductance is \(U = 1/0.25 = 4\) W/K, meaning 4 watts flow per kelvin of temperature difference across the panel.
Typical Thermal Conductivity Values (k) of Common Materials
The table lists approximate thermal conductivity k in W/(m·K) at about 20–25 °C. Use it to pick a starting value for the conductivity field. A lower k means the material resists heat flow better.
| Material | k (W/m·K), approx. |
|---|---|
| Copper | 385–400 |
| Aluminium | 205–237 |
| Carbon steel | 45–54 |
| Stainless steel | about 15 |
| Concrete | 1.0–1.7 |
| Glass | about 1.0 |
| Brick | 0.6–1.0 |
| Water | about 0.6 |
| Softwood (across the grain) | 0.12–0.15 |
| Expanded polystyrene (EPS) | 0.033–0.040 |
| Mineral wool / fibreglass | 0.032–0.044 |
| Polyurethane foam | 0.022–0.028 |
| Still air | about 0.026 |
Note: these are typical values, not guarantees. Real conductivity changes with density, moisture content, temperature and manufacturing. Damp insulation, for example, conducts noticeably more heat. For design work, use the manufacturer's declared value or the value given in the relevant standard.
Comparing Resistance Across Materials and Thicknesses
All cases use a fixed area of A = 1 m². Thermal resistance is R = L / (k·A) in K/W. Conductance is G = 1/R in W/K.
| Case | L (m) | k (W/m·K) | R (K/W) | Conductance (W/K) |
|---|---|---|---|---|
| Foam | 0.1 | 0.04 | 2.5 | 0.4 |
| Concrete | 0.1 | 1.4 | 0.0714 | 14 |
| Copper | 0.01 | 400 | 0.000025 (2.5×10⁻⁵) | 40,000 |
| Glass | 0.005 | 1.0 | 0.005 | 200 |
| Fibreglass | 0.2 | 0.04 | 5 | 0.2 |
Effect of doubling thickness or area (foam example)
| Change from the 0.1 m foam, 1 m² case | R (K/W) | Conductance (W/K) |
|---|---|---|
| Baseline: L = 0.1 m, A = 1 m² | 2.5 | 0.4 |
| Double thickness: L = 0.2 m, A = 1 m² | 5 (R doubles) | 0.2 |
| Double area: L = 0.1 m, A = 2 m² | 1.25 (R halves) | 0.8 |
R is proportional to thickness and inversely proportional to both conductivity and area. A 1 m² slab of 0.1 m foam resists heat flow about 35 times more than the same thickness of concrete (2.5 vs 0.0714 K/W). A thin copper plate offers almost no resistance.
Calculating Layered (Series) Thermal Resistance by Hand
- Convert to SI units. Use thickness in metres (1 cm = 0.01 m, 1 mm = 0.001 m), area in m² and k in W/(m·K).
- Compute each layer's resistance: \(R_i = \dfrac{L_i}{k_i A}\).
- Sum for a series stack (heat passing through layer after layer, over the same area): \(R_{total} = R_1 + R_2 + \dots + R_n\).
- Compute conductance: \(G = \dfrac{1}{R_{total}}\) in W/K.
- Optionally find heat flow: \(Q = \dfrac{\Delta T}{R_{total}}\) in watts, where ΔT is the temperature difference across the whole stack.
Parallel paths: when heat can flow through several side-by-side paths (for example, studs next to insulation), combine them as \(\dfrac{1}{R_{total}} = \sum \dfrac{1}{R_i}\). Parallel paths make the total resistance lower than the smallest single path.
Two-layer example
A wall section of area A = 2 m² has a 0.10 m fibreglass layer (k = 0.04 W/m·K) and a 0.15 m concrete layer (k = 1.4 W/m·K). The temperature difference is 20 K.
- Fibreglass: \(R_1 = \dfrac{0.10}{0.04 \times 2} = \dfrac{0.10}{0.08} = \)1.25 K/W
- Concrete: \(R_2 = \dfrac{0.15}{1.4 \times 2} = \dfrac{0.15}{2.8} \approx 0.0536\) K/W
- Total: \(R_{total} = 1.25 + 0.0536 \approx 1.304\) K/W
- Conductance: \(G = \dfrac{1}{1.304} \approx 0.767\) W/K
- Heat flow: \(Q = \dfrac{20}{1.304} \approx 15.3\) W
The insulation layer accounts for about 96% of the total resistance, so improving it matters far more than changing the concrete. This calculation covers conduction only and ignores surface (air-film) resistances, convection and radiation.
FAQ
What units does this use? SI units: metres, W/m·K, and m², giving resistance in K/W.
What's the difference between R-value and this R? Building "R-value" is often the area-normalised resistance (\(R = L/k\), units m²·K/W). This calculator includes area, giving the absolute resistance of the whole component in K/W.
Can I add layers? Yes — for layers in series, the total resistance is the sum of each layer's R.