What is the Three-Phase Current Calculator?
This tool computes the line current (in amperes) drawn by a balanced three-phase load. It uses the standard power equation for three-phase systems, relating real power, line-to-line voltage and power factor. It applies universally to any balanced three-phase AC system regardless of country, though typical line voltages are 400 V (Europe) or 480 V (North America).
How to use it
Enter the load's real power in watts, the line-to-line (phase-to-phase) voltage, and the power factor (a value between 0 and 1, typically 0.8–0.95 for motors). The calculator returns the line current in amps, along with the real power in kW and the apparent power in kVA.
The formula explained
For a balanced three-phase load: $$I = \frac{P}{\sqrt{3} \times V \times PF}$$, where P is real power in watts, V is the line-to-line voltage, PF is the power factor, and \(\sqrt{3} \approx 1.732\). The \(\sqrt{3}\) factor arises because line current relates to phase quantities through the geometry of three-phase systems. Apparent power \(S = P / PF\) gives the kVA, which is what transformers and generators must be sized for.
Worked example
A 10,000 W motor on a 400 V three-phase supply with a power factor of 0.9: $$I = \frac{10000}{1.732 \times 400 \times 0.9} = \frac{10000}{623.5} \approx 16.04 \text{ A}$$ The apparent power is \(10 / 0.9 \approx 11.11\) kVA.
Typical Three-Phase Current by Power and Voltage
The table shows balanced three-phase line current in amps at a power factor of 0.9, using \(I = \dfrac{P}{\sqrt{3} \times V \times PF}\) with P as real power in watts and V as line-to-line voltage. Values are rounded to 1 decimal. Efficiency is not included, so P is treated as the electrical input power.
| Power | 230 V (A) | 400 V (A) | 480 V (A) | 690 V (A) |
|---|---|---|---|---|
| 5 kW | 13.9 | 8.0 | 6.7 | 4.6 |
| 10 kW | 27.9 | 16.0 | 13.4 | 9.3 |
| 22 kW | 61.4 | 35.3 | 29.4 | 20.5 |
| 37 kW | 103.2 | 59.3 | 49.4 | 34.4 |
| 55 kW | 153.4 | 88.2 | 73.5 | 51.1 |
| 75 kW | 209.2 | 120.3 | 100.2 | 69.7 |
Example (22 kW at 400 V): \(I = \dfrac{22000}{1.732 \times 400 \times 0.9} = \dfrac{22000}{623.5} \approx 35.3\ \text{A}\). Doubling the voltage roughly halves the current for the same power.
Typical Power Factor Values by Load Type
Power factor depends on the load. The figures below are typical ranges only; the actual value for your equipment should come from its nameplate or datasheet.
| Load type | Typical power factor |
|---|---|
| Resistive heaters, incandescent lighting | about 1.0 |
| Induction motors at full load | about 0.8–0.9 |
| Induction motors at light load or unloaded | about 0.2–0.5 |
| LED lighting and electronic drives | 0.9–0.95 |
| Fluorescent lighting with magnetic ballast | 0.5–0.8 |
Many electricity utilities require or reward a power factor of roughly 0.9 or higher and may charge penalties below it. The exact threshold varies by utility and country, so check your supplier's tariff terms.
FAQ
Which voltage do I enter? Use the line-to-line voltage (e.g. 400 V or 480 V), not the phase-to-neutral voltage.
What if I have kW instead of W? Multiply kW by 1000 to get watts before entering.
What power factor should I use? For resistive loads use 1.0; for induction motors 0.8–0.9 is common. Check the equipment nameplate when in doubt.