Greenhouse Heating Requirement Calculator

Greenhouse Heating Requirement Calculator

Growing AI Skill PRO

Enter Calculation

Single glass / film ≈ 6.0, twin-wall polycarbonate ≈ 3.0, double glazing ≈ 2.8, insulated panel ≈ 1.5
Tight new house ≈ 0.5–1.0, older structure ≈ 1.5–3.0

Formula

Q=U-value·A·ΔT+0.33·ACH·V·ΔTwhere{h=Ridge (m)−Gutter (m)A=2Gutter (m)(L (m)+W (m))+W (m)h+2L (m)(W (m)2)2+h2V=L (m)W (m)(Gutter (m)+h2)ΔT=Inside (° C)−Outside (° C)\begin{gathered} Q = \text{U-value} \cdot A \cdot \Delta T + 0.33 \cdot \text{ACH} \cdot V \cdot \Delta T \\[1.5em] \text{where}\quad \left\{ \begin{aligned} h &= \text{Ridge (m)} - \text{Gutter (m)} \\ A &= 2\,\text{Gutter (m)}\left(\text{L (m)} + \text{W (m)}\right) + \text{W (m)}\,h + 2\,\text{L (m)}\sqrt{\left(\tfrac{\text{W (m)}}{2}\right)^{2} + h^{2}} \\ V &= \text{L (m)}\,\text{W (m)}\left(\text{Gutter (m)} + \tfrac{h}{2}\right) \\ \Delta T &= \text{Inside (\degree C)} - \text{Outside (\degree C)} \end{aligned} \right. \end{gathered}
Show calculation steps (1)
  1. Output Units (kW and BTU/h)

    QkW=Q1000QBTU/h=Q×3.412142where{Q=total heat loss in wattsQAfloor=QL (m)×W (m)\begin{gathered} Q_{kW} = \frac{Q}{1000} \qquad Q_{BTU/h} = Q \times 3.412142 \\[1.5em] \text{where}\quad \left\{ \begin{aligned} Q &= \text{total heat loss in watts} \\ \frac{Q}{A_{floor}} &= \frac{Q}{\text{L (m)} \times \text{W (m)}} \end{aligned} \right. \end{gathered}

    kW = watts / 1000; BTU/h = watts x 3.412142; watts per square metre of floor uses L x W

Usage stats

Advertisement

Results

Required Heater Output
45.7
kilowatts (kW) to hold the target temperature
Total heat loss (watts)
45,703 W
Total heat loss (BTU/hr)
155,945
Conduction loss through glazing 40,693.45 W
Infiltration (air change) loss 5,009.4 W
Glazed envelope area (walls, gables, roof) 294.88 m²
Enclosed air volume 440 m³
Temperature lift (ΔT) 23 K
Heat per m² of floor 285.64 W/m²
Steady-state estimate for a still, dark night: the floor/ground loss, thermal screens, wind exposure and solar gain are not modelled. Size the heater at or slightly above this figure and add 10–20% margin for windy sites.

Report an error on this page

What this calculator does

A greenhouse loses heat all night through its glazing and through air leakage. This tool estimates the continuous heater output needed to hold a chosen inside temperature on your coldest design night. It works in metric units (metres, °C, W/m²·K) and reports the answer in kilowatts, watts and BTU/hr so you can match it to any heater rating plate.

How to use it

Enter the length, width, side (gutter) height and ridge height of an even-span greenhouse. The calculator derives the glazed envelope area \(A\) (two side walls, two gable ends and both roof slopes) and the enclosed volume \(V\) for you. Then give the glazing U-value \(U\), the air changes per hour \(n\), your target inside temperature and the coldest outside temperature you want to design for.

Cross-section of a gable greenhouse with width, length, wall height, ridge rise and roof slope marked
Greenhouse geometry: gutter height, ridge rise and roof slope set both the glazing area and the internal volume.

The formula explained

Total steady-state loss is conduction plus infiltration:

$$Q = U \times A \times \Delta T + 0.33 \times n \times V \times \Delta T$$

where \(\Delta T\) = inside minus outside temperature in kelvin, \(U\) = glazing heat transfer coefficient in W/m²·K, \(A\) = glazed area in m², \(n\) = air changes per hour and \(V\) = volume in m³. The roof slope length comes from Pythagoras: \(s = \sqrt{(W/2)^2 + r^2}\) with \(r\) the ridge rise above the gutter.

Advertisement
Diagram showing conduction heat loss through glazing and ventilation heat loss from air exchange
Total heat demand is conduction through the glazing (orange) plus heat carried away by air changes (blue), both driven by the inside–outside temperature difference.

Worked example

A 20 m × 8 m house, 2 m to the gutter and 3.5 m to the ridge, single glazed (\(U = 6\)), 1.5 air changes per hour, held at 18 °C when it is −5 °C outside. The slope is \(\sqrt{4^2 + 1.5^2} = 4.272\) m, so the area is

$$A = 112 + 12 + 170.88 = 294.88\,\text{m}^2$$

and the volume is 440 m³. With \(\Delta T = 23\) K:

$$Q = 6 \times 294.88 \times 23 + 0.33 \times 1.5 \times 440 \times 23 = 40693 + 5009 = 45.7\,\text{kW}$$

Glazing U-Values and Air Change Rates

The calculator needs two numbers that describe the greenhouse envelope: the glazing U-value (thermal transmittance, in W/m²·K) and the infiltration rate (air changes per hour, ACH or \(n\)). The first drives the fabric loss \(U \cdot A \cdot \Delta T\); the second drives the ventilation loss \(0.33 \cdot n \cdot V \cdot \Delta T\), where 0.33 Wh/m³·K is the volumetric heat capacity of air.

Table 1 — Typical glazing U-values

Glazing / cladding U-value (W/m²·K) Notes
Horticultural single glass (3–4 mm) 6.0–6.4 Baseline for traditional glasshouses
Single-skin acrylic or rigid PVC sheet ≈5.7 Slightly better than glass, lower rigidity
Twin-wall polycarbonate, 6–10 mm 3.3 (6 mm) – 3.0 (10 mm) Most common hobby/commercial upgrade
Triple-wall polycarbonate, 16 mm ≈2.4 Lowest loss, highest light diffusion
Double-glazed sealed unit ≈2.8 Heavy; needs a stronger frame
Single glass + internal thermal screen (closed) 3.0–3.5 Night-time value only; screen open reverts to ~6.0
Single polythene film ≈6.8 Worst case; high radiant loss on clear nights
Double-inflated polythene ≈4.0 Requires a running inflation fan

Table 2 — Air changes per hour by construction and condition

Construction / condition ACH (\(n\), h⁻¹)
New sealed glasshouse, tight vents and doors 0.5–1.0
Well-maintained glass house, sound seals 1.0–1.5
Older glass, lapped/unsealed panes, worn vent seals 2.0–3.0
Plastic film house, well sealed at ground and ends 0.5–1.0
Exposed, windy site (adjustment) add ≈0.5–1.0

Every row in both tables is a design estimate for still-air or nominal design conditions, not a measured value for your structure. The figures follow the conventions used in horticultural engineering references such as UK AHDB/Grower protected-cropping energy guidance and the ASABE EP406 series on heating and ventilating greenhouses in the United States; individual manufacturers publish tested U-values for their own panels and those should be preferred when available.

Wind raises both terms. The external surface resistance falls as wind speed rises, so a glazing rated at 6.0 W/m²·K in still air can behave like 6.5–7.0 W/m²·K in a strong wind, and wind pressure also forces more air through laps, vent edges and door gaps — which is why the exposed-site row adds to \(n\) rather than replacing it. On a sheltered site the lower end of each range is reasonable; on an open, coastal or hilltop site use the upper end, and if you are unsure, size on the higher figure.

Advertisement

Typical Target Temperatures and Design Conditions

Inside temperature: recommended minimum night temperatures

Enter the minimum night temperature the crop must hold, not a comfortable daytime figure — heating plant is sized for the coldest hour, not the average. The bands below reflect long-standing UK/European protected-cropping practice (RHS and AHDB horticultural guidance) and are widely used in North America as well.

Use Minimum night temperature
Frost-free storage / overwintering hardy stock 2–5 °C
Tender overwintering (pelargonium, fuchsia) 5–7 °C
General propagation and seed raising 13–16 °C
Tomato, cucumber, pepper production 16–18 °C night, 18–24 °C day
Tropical foliage and orchid houses 18–21 °C

Outside temperature: use a winter design dry-bulb, not a mean

The correct outside figure is the winter design dry-bulb temperature for your location — the 99% or 99.6% annual heating design condition tabulated in the ASHRAE Handbook of Fundamentals climatic design tables (the basis used in the US and Canada, and reproduced for stations worldwide). A monthly or seasonal mean is far too mild and will undersize the heater. Approximate 99% values, for orientation only — always look up your nearest station:

  • Southern England / southern UK: ≈ −4 to −6 °C
  • Northern England, Scotland: ≈ −8 to −10 °C
  • Atlanta, Georgia (US): ≈ −6 °C
  • Denver, Colorado (US): ≈ −17 °C
  • Chicago, Illinois (US): ≈ −18 °C
  • Minneapolis, Minnesota (US): ≈ −23 °C

These are national/regional figures tied to specific weather stations and standards; they are not universal, and a greenhouse in a frost hollow or on an exposed ridge can sit several kelvin below the nearest airport station.

Design ΔT and the sizing margin

Most greenhouse sizing in temperate climates ends up with a design temperature lift of

$$\Delta T = T_{\text{in}} - T_{\text{out}} \approx 20\text{–}30\ \text{K}$$

A ΔT much below 20 K usually means a frost-free target or a mild location; much above 30 K means a cold-continental site or a tropical house, and at that point glazing upgrades and a thermal screen are normally cheaper than the extra heater capacity plus fuel. On top of the calculated load it is conventional to add a 10–20% margin for wind exposure, degraded seals, control overshoot, heater derating at altitude, and the reserve needed to recover temperature after a cold night's vent opening.

Worked check

A 6.0 m × 3.0 m even-span house with a 1.8 m gutter and 2.5 m ridge, glazed in 6 mm twin-wall polycarbonate (\(U = 3.3\)) at \(n = 1.0\) ACH, holding 16 °C against a −5 °C design outside temperature, gives \(\Delta T = 21\) K, \(A \approx 54.4\ \text{m}^2\) and \(V \approx 38.7\ \text{m}^3\):

$$Q = 3.3 \cdot 54.36 \cdot 21 + 0.33 \cdot 1.0 \cdot 38.7 \cdot 21 = 3767 + 268 = 4036\ \text{W}$$

That is 4.04 kW, or roughly 13,800 BTU/hr — so with a 15% margin you would specify a heater of about 4.6 kW (≈15,800 BTU/hr) and choose the next size up in the range available.

This section is general engineering guidance for sizing, not a substitute for advice from a heating engineer or your local building and fuel-appliance regulations, which govern flueing, combustion air and gas or oil installation.

FAQ

Which outside temperature should I use? Use the coldest night you realistically expect, not the winter average — typically the 99% design temperature for your area.

Why is my figure so large? Single glazing and leaky vents dominate the result. Halving the U-value with twin-wall polycarbonate or a thermal screen roughly halves the heater size.

Should I add a safety margin? Yes — add 10–20% for exposed, windy sites or if you use the crop space for frost-sensitive plants, since the model ignores wind-driven losses and ground conduction.