What this calculator does
A psychrometer uses two thermometers — a dry bulb that measures the ordinary air temperature and a wet bulb wrapped in a moist wick. Evaporation from the wick cools the wet bulb, and the size of that cooling depends on how dry the air is. This calculator converts those two readings into relative humidity (RH), the percentage of moisture the air holds relative to the maximum it could hold at the dry-bulb temperature.
How to use it
Enter the dry-bulb temperature, the wet-bulb temperature (always equal to or lower than the dry bulb), and the local atmospheric pressure in hectopascals (sea-level standard is 1013.25 hPa). The tool returns the relative humidity along with the saturation vapour pressures and the actual vapour pressure of the air.
The formula explained
The result uses the psychrometric equation:
$$RH = 100 \times \frac{e_{s}(T_w) - A \cdot P \cdot (T - T_w)}{e_{s}(T)}$$
where \(T\) is the dry-bulb temperature, \(T_w\) the wet-bulb temperature, \(P\) the pressure, and \(A \approx 0.000662\ \text{°C}^{-1}\) the psychrometer constant. The saturation vapour pressure \(e_{s}\) at any temperature \(t\) (°C) comes from the Magnus–Tetens relation $$e_{s}(t) = 6.112 \cdot \exp\!\left(\frac{17.67 \cdot t}{t + 243.5}\right)$$ in hPa.
Worked example
For \(T = 25\,\text{°C}\), \(T_w = 18\,\text{°C}\), \(P = 1013.25\,\text{hPa}\): \(e_{s}(25) \approx 31.67\,\text{hPa}\) and \(e_{s}(18) \approx 20.62\,\text{hPa}\). The actual vapour pressure $$e = 20.62 - 0.000662 \times 1013.25 \times (25 - 18) \approx 20.62 - 4.70 = 15.93\,\text{hPa}.$$ So $$RH = 100 \times \frac{15.93}{31.67} \approx 50.3\%.$$
Interpreting Your Relative Humidity Result
Relative humidity (RH) is the amount of water vapour in the air as a percentage of the maximum it could hold at the same temperature and pressure. The result is a ratio of actual vapour pressure to saturation vapour pressure at the dry-bulb temperature.
| RH band | General meaning |
|---|---|
| Below 30% | Dry air. Evaporation is fast and the wet-bulb reading is far below the dry-bulb reading. |
| 30–60% | The range commonly cited for indoor comfort in ASHRAE Standard 55 guidance (a US-originated standard used internationally). |
| Above 60% | Humid air. Evaporation is slow and the wet-bulb reading is close to the dry-bulb reading. |
| 100% | Saturated air. Fog, cloud or dew can form, and wet-bulb equals dry-bulb. |
Wet-bulb depression is \(T_d - T_w\). A small depression means the air is close to saturation and RH is high. A large depression means water evaporates readily from the wet wick, so RH is low.
RH depends on temperature. The same amount of water vapour gives a different RH at different temperatures, because saturation vapour pressure rises steeply with temperature. Air at 20 °C and 50% RH, when warmed to 30 °C with no added moisture, drops to about 27% RH. Always quote RH together with the air temperature.
Readings are only as good as the measurement: the wick must be clean and wet, the thermometers accurate, and there must be adequate airflow over the wet bulb.
RH Across Different Dry- and Wet-Bulb Readings
All rows use standard sea-level pressure (1013.25 hPa), so the psychrometer term is \(0.000662 \times 1013.25 \approx 0.6708\) hPa per °C of depression. Saturation vapour pressure is \(e(T) = 6.112\,e^{17.67T/(T+243.5)}\) in hPa.
| Dry bulb (°C) | Wet bulb (°C) | Depression (°C) | Computed RH |
|---|---|---|---|
| 20 | 20 | 0 | 100% |
| 20 | 18 | 2 | 82.5% |
| 25 | 18 | 7 | 50.3% |
| 30 | 24 | 6 | 60.8% |
| 40 | 25 | 15 | 29.2% |
Worked check (25 °C dry, 18 °C wet):
- \(e_d = 6.112\,e^{17.67\times 25/(25+243.5)} = 6.112\,e^{1.6453} \approx 31.67\) hPa
- \(e_w = 6.112\,e^{17.67\times 18/(18+243.5)} = 6.112\,e^{1.2163} \approx 20.63\) hPa
- \(RH = 100 \times \dfrac{20.63 - 0.6708\times 7}{31.67} = 100 \times \dfrac{15.93}{31.67} \approx 50.3\%\)
The hot, dry case (40 °C dry, 25 °C wet) shows that a large depression gives low RH. The 20/20 case shows that zero depression means saturation.
Constants Used in the Calculation
| Constant | Value | Role |
|---|---|---|
| Psychrometer constant \(A\) | ≈ 0.000662 °C−1 | Scales the wet-bulb depression into a vapour-pressure correction; this value is typical of a well-ventilated (aspirated) psychrometer |
| Magnus–Tetens coefficient | 6.112 hPa | Saturation vapour pressure at 0 °C |
| Magnus–Tetens coefficient | 17.67 | Exponent scaling factor (dimensionless) |
| Magnus–Tetens coefficient | 243.5 °C | Temperature offset in the exponent |
| Standard sea-level pressure | 1013.25 hPa | Default total pressure \(P\) |
Psychrometric equation: \(e = e_w - A\,P\,(T_d - T_w)\), where \(e\) is the actual vapour pressure, \(e_w\) is the saturation vapour pressure at the wet-bulb temperature, and \(P\) is the total pressure in hPa.
Variation of \(A\): it is not a universal constant. It depends on airflow over the wet bulb, thermometer size and type, and wick condition. Poorly ventilated or still-air instruments need a larger value, so using 0.000662 with them will bias the result. Follow your instrument manufacturer's coefficient where one is given.
Valid range: this Magnus form (the Bolton 1980 coefficients) is generally quoted as accurate to a fraction of a percent for roughly −35 °C to +35 °C, over liquid water. Outside that range, and especially below 0 °C where the wet bulb may be coated with ice, errors grow and the result should be treated as approximate.
Pressure: at higher altitude, use the actual station pressure instead of 1013.25 hPa. Lower pressure shrinks the correction term slightly and raises the computed RH for the same readings.
FAQ
Why must the wet bulb be cooler? Evaporation removes heat, so unless the air is fully saturated the wet bulb always reads lower; if the readings are equal, RH is 100%.
What pressure should I enter? Use your local station pressure if known; otherwise the standard 1013.25 hPa is a good approximation near sea level.
How accurate is it? The psychrometer constant assumes a properly ventilated (aspirated) wet bulb; poor airflow can bias results, so results are accurate to a few percent in normal conditions.