Transformer Breaker Size Calculator (US NEC)

Transformer Breaker Size Calculator (US NEC)

Growing AI Skill PRO

Enter Calculation

Formula

Breakerpri=⌈Ip×Multiplier (%)100⌉NEC stdwhere{Ip=1000×Size (kVA)3×Primary (V)Is=1000×Size (kVA)3×Secondary (V)Breakersec=⌈1.25×Is⌉NEC std\begin{gathered} \text{Breaker}_{\text{pri}} = \left\lceil I_{p} \times \frac{\text{Multiplier (\%)}}{100} \right\rceil_{\text{NEC std}} \\[1.5em] \text{where}\quad \left\{ \begin{aligned} I_{p} &= \frac{1000 \times \text{Size (kVA)}}{\sqrt{3} \times \text{Primary (V)}} \\ I_{s} &= \frac{1000 \times \text{Size (kVA)}}{\sqrt{3} \times \text{Secondary (V)}} \\ \text{Breaker}_{\text{sec}} &= \left\lceil 1.25 \times I_{s} \right\rceil_{\text{NEC std}} \end{aligned} \right. \end{gathered}
Usage stats

Advertisement

Results

Primary Circuit Breaker Size
125 A
next standard size at or above the calculated current (112.76 A)
Secondary Circuit Breaker Size (125% of secondary FLA)
300 A
Primary full-load current (FLA) 90.21 A
Secondary full-load current (FLA) 208.18 A
Primary protection multiplier 125 %
Calculated primary trip current 112.76 A
Calculated secondary trip current 260.22 A
Based on US NEC Article 450.3(B) and the standard overcurrent device ratings of NEC 240.6(A). Estimate only - conductor ampacity, inrush, continuous load, ambient derating and local amendments must be verified by a licensed electrical engineer.

Report an error on this page

What This Calculator Does

This tool applies the United States National Electrical Code (NEC), Article 450.3(B) for transformer overcurrent protection and Article 240.6(A) for standard device ratings. Figures assume a dry-type or liquid-filled power transformer of 1000 V or less unless a higher multiplier is selected. Outside the US, check your own code (for example CEC in Canada or IEC/BS 7671 practice in Europe), because the multipliers differ.

One-line diagram showing a breaker above a transformer and a breaker below it feeding a load
Primary and secondary overcurrent protection sit on opposite sides of the transformer and are sized separately.

How To Use It

Enter the transformer nameplate rating in kVA, choose single-phase or three-phase, then enter the primary and secondary voltages. Pick the protection multiplier: 125% is the normal case where a separate secondary overcurrent device is installed; 167% applies when the primary device is the only protection.

The Formula Explained

Full-load current is nameplate power divided by voltage, with a line-to-line factor for three-phase:

$$I_{FLA} = \frac{kVA \times 1000}{V \times \sqrt{3}}$$

where \(kVA\) = transformer rating, \(V\) = winding voltage, and the \(\sqrt{3}\) term is dropped for single-phase. The breaker trip current is then \(I_{breaker} = I_{FLA} \times \tfrac{M}{100}\), with \(M\) the NEC multiplier, rounded up to the next standard rating (15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 400 A and so on).

Advertisement
Three-step flow from transformer rating to current calculation to rounded-up breaker size
The calculator converts kVA to current, applies the NEC multiplier, then rounds to the next standard breaker size.

Worked Example

A 75 kVA three-phase transformer, 480 V primary, 208 V secondary, 125% multiplier:

$$I_{FLA} = \frac{75 \times 1000}{480 \times \sqrt{3}} = 90.21\,\text{A}$$$$I_{breaker} = 90.21 \times 1.25 = 112.76\,\text{A} \rightarrow 125\,\text{A}$$

The secondary carries \(75000 / (208 \times \sqrt{3}) = 208.18\) A, so \(208.18 \times 1.25 = 260.22\) A rounds up to a 300 A secondary breaker.

Standard Breaker Ratings and Transformer Full-Load Currents

1. NEC 240.6(A) standard ampere ratings

In the United States, a calculated protection value is rounded to one of these standard ratings for fuses and inverse-time circuit breakers. Devices with ratings other than these (for example 13 A or 260 A) exist but are not "standard" for the purposes of the next-higher-size rules.

Standard ampere ratings, NEC 240.6(A)
Range Standard ratings (A)
15 – 100 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100
110 – 600 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600
700 – 6000 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000, 6000

NEC 240.6(B) and (C) additionally treat the adjusted setting of an adjustable-trip breaker as its rating, with restricted access to the adjustment means required in some cases.

2. Full-load current by transformer size

Currents below are rated full-load amperes computed directly from the kVA and voltage:

$$I_{3\phi} = \frac{\text{kVA} \times 1000}{V \times 1.732}, \qquad I_{1\phi} = \frac{\text{kVA} \times 1000}{V}$$

For a 45 kVA unit at 480 V three-phase, \(I = \dfrac{45 \times 1000}{480 \times 1.732} = \dfrac{45000}{831.4} = 54.1\ \text{A}\). Values are rounded to one decimal place; always confirm against the transformer nameplate, which is the governing figure.

Rated full-load current (A) — line current for three-phase, load current for single-phase
Transformer (kVA) 480 V, 3-phase 208 V, 3-phase 240 V, 1-phase
15 18.0 41.6 62.5
25 30.1 69.4 104.2
30 36.1 83.3 125.0
45 54.1 124.9 187.5
75 90.2 208.2 312.5
112.5 135.3 312.3 468.8
150 180.4 416.4 625.0
225 270.7 624.6 937.5
300 360.9 832.7 1250.0
500 601.4 1387.9 2083.3
750 902.1 2081.8 3125.0

The kVA values listed are common US dry-type distribution sizes; 480 V and 208 V (208Y/120) are standard US three-phase system voltages and 240 V single-phase is a common US secondary. The larger single-phase entries are shown for arithmetic reference only — 500 and 750 kVA single-phase units at 240 V are rare in practice. In regions using 400 V / 230 V systems the same formulas apply, but the NEC multipliers in the previous section do not.

Advertisement

Interpreting Your Breaker Sizes

The numbers this calculator returns are maximum permitted overcurrent device ratings for protecting the transformer itself, under US NEC 450.3(B). They are not a conductor sizing result, not a load calculation, and not a short-circuit or arc-flash study.

It is a maximum, not a required size

Because 450.3(B) sets ceilings, any smaller standard rating is acceptable as long as it carries the actual connected load without nuisance tripping and still protects the conductors it feeds. Conductors are sized separately under Article 310 and the applicable ampacity and adjustment rules; a device that satisfies 450.3(B) may be far larger than what the feeder conductors can be protected at, so both checks must pass.

Inrush is the practical constraint on the primary device

Energizing a transformer draws a magnetizing inrush current that is typically on the order of 8–12 times full-load current for a few cycles (the exact magnitude and decay depend on the design, residual core flux and the point on the voltage wave at closing). A thermal-magnetic breaker sized at 125% of FLA can trip on this transient, which is why an instantaneous-trip or magnetic-only breaker with an adjustable instantaneous setting, or a time-delay (dual-element) fuse, is often used on the primary. Note that a magnetic-only breaker provides no overload function on its own, so the code path chosen must supply that protection elsewhere — commonly via a secondary overcurrent device.

Worked example: 75 kVA, 480 V to 208Y/120 V, three-phase

Primary full-load current:

$$I_p = \frac{1000 \times 75}{\sqrt{3} \times 480} = \frac{75000}{831.4} = 90.2\ \text{A}$$

At the 125% primary-only row, \(90.2 \times 1.25 = 112.8\ \text{A}\); the next higher standard rating in 240.6(A) gives a primary breaker of 125 A. On the secondary, \(I_s = 75000 / (\sqrt{3} \times 208) = 208.2\ \text{A}\) and \(208.2 \times 1.25 = 260.3\ \text{A}\), rounding up to a 300 A secondary device.

The secondary device usually does double duty

The secondary overcurrent device that satisfies 450.3(B) is normally the same device that protects the secondary conductors under NEC 240.21(C), which governs transformer secondary conductors and their tap allowances. If you rely on a tap rule instead of a device at the transformer, the conductor length, ampacity and termination requirements of the specific 240.21(C) subsection must all be met — a compliant 450.3(B) number does not by itself make a secondary tap legal.

Fuses and breakers use the same multipliers

Table 450.3(B) does not distinguish between fuses and circuit breakers for transformers 1000 V or less; the 125%, 167%, 250% and 300% figures apply to either. The distinction between fuse and breaker multipliers appears in 450.3(A), for transformers over 1000 V. Fuse class and breaker trip curve still matter enormously for inrush ride-through and for selective coordination even though the sizing ceiling is identical.

Verify against the nameplate and the AHJ

  1. Use the transformer nameplate ratings — kVA, voltages, impedance, and any listed primary/secondary protection requirements — as the governing input, not catalog or nominal figures.
  2. Confirm the result with the authority having jurisdiction (AHJ). Local amendments, the adopted NEC edition, and inspector interpretation all vary by state and municipality in the US.
  3. Check that the device's interrupting rating exceeds the available fault current, and that the enclosure and terminations are rated for the conductors used.

This article is general reference information about a US code rule, not engineering advice for a specific installation. Transformer and overcurrent protection design should be reviewed by a licensed electrician or professional engineer familiar with the code edition in force at your site.

FAQ

Can I round up to the next standard size? Yes. NEC 450.3(B) permits the next higher standard rating when 125% of full-load current does not match a standard device, for currents of 9 A or more.

Why is the secondary breaker larger than the primary? A step-down transformer keeps power roughly constant, so lower secondary voltage means proportionally higher current.

Does this size the conductors too? No. Feeder conductors must be sized separately for ampacity, temperature derating and voltage drop, and the breaker must protect them.